Controller Ratings - Toshiba JK 400 Series Instruction Manual

Ampere medium voltage controllers fixed type 7.2kv maximum
Hide thumbs Also See for JK 400 Series:
Table of Contents

Advertisement

Basic Installation and Operation Guide
Interrupting
Capacity
(Sym.
Amperes)
200@2.3kV
50,000 RMS
350@4.0kV
@2.3-6.6kV
400@4.6kV
(7.2kV Max)
570@6.6kV
Enclosure Type
One-High Controller
Type-1
Ventilated
Type-1 Non-
Ventilated
Type-12, 3R
TOSHIBA

CONTROLLER RATINGS

Table 2 Short-Circuit & Withstand Capability
Interrupting
Short Time
Capacity
Capability
(Sym. MVA)
30 Seconds
2400 A
Table 3 Continuous Current Rating
Max. Continuous
Max. Continuous Amperes
Amperes
Lower Controller in a Two-
High Stacking Arrangement
360
320
310
JK 400 Series Fixed Controllers
Short Time
Dielectric
Capability
Withstand
1 Second
1 Minute
AC 19 kV
6,000 A
DC 26kV
Max. Continuous Amperes
Upper Controller in a Two-High
360
320
310
Impulse
Voltage
Withstand
60 kV BIL
Stacking Arrangement
320
280
280