Motor-side power components
7.4 dv/dt filter compact plus voltage peak limiter
7.4.4
Connecting the dv/dt filter compact plus Voltage Peak Limiter
Figure 7-18
Connecting the dv/dt filter compact plus voltage peak limiter - integrated unit
Figure 7-19
Connecting the dv/dt filter compact plus voltage peak limiter - separate components
Cable cross-sections
In a dv/dt filter with separate voltage peak limiter (Type 4), the connections between dv/dt
reactor and voltage peak limiter are already installed on the voltage peak limiter.
Table 7- 24
dv/dt filter compact plus volt-
218
Cable cross-sections for connections between a dv/dt filter and Motor Module
Cross-section
age peak limiter
Type 1
Type 2
[mm²]
16
25
Water-cooled chassis power units for common cooling circuits
Connection on dv/dt filter
M8 screw/12 Nm
M8 screw/12 Nm
Manual, 08/2017, 6SL3097-4AM10-0BP0