Derating Factors As A Function Of The Ambient Temperature - Siemens SINAMICS S120 Equipment Manual

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules
6.6 Technical specifications
6.6.2.2

Derating factors as a function of the ambient temperature

The units can supply 100 % output current at an ambient air temperature of between 0 °C
and 45 °C. The maximum output current decreases linearly to 90 % at ambient air
temperatures of between 45 °C and 50 °C.
Figure 6-18
172
Maximum current as a function of ambient temperature
Water-cooled chassis power units for common cooling circuits