Building Technologies
CPS Fire Safety
Limits and restrictions
Type
Version
MM8000
MP4.81
MK8000
® * See section 4.4 for details on interactions.
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
Restrictions
NK823x supports logical connections to a max. of 4
hosts via proprietary CMSDL/IP protocol OR via
BACnet/IP protocol
Dial-up via CEI protocol and network-wide-
interactions* via BACnet are currently not compatible
FS20/FS720/STT20 supported by NK823x only
- Limit 10,000 detectors in an FS20/FS720 system
- Limit: Max. 16 FS20/FS720 units or 12 FS20/FS720
and 10 STT20 units
Only one CS6 Guarto intrusion panel per NK823x is
supported (CS6 connected via USB and Echelon U10
USB Network Interface - TP/FT-10 Channel to
NK823x)
NK8000 requires static IP-addresses (i.e. DHCP is not
supported)
Default UDP Port 47808 (hex BAC0) for BACnet con-
nectivity (configurable)
BACnet Broadcast Management Device (BBMD) is
supported in NK823x (NK823x can be installed on dif-
ferent TCP/IP subnets)
The NK823x can be configured as a BACnet Foreign
Device for FS20/FS720
Automation level configurations
55
09.2016