Current Carrying Capacity of the DC Link Busbar

2.3
The current carrying capacity of the DC link busbar must be observed for the configuring and
the construction of the drive group.
The maximum current carrying capacity of the DC link busbar differs depending on the width
of the power units.
● For power units from 3 A to 60 A (max. width 150 mm) and DC link components (Braking,
● For power units from 85 A to 200 A (200 / 300 mm width), the DC link busbar can be
If the current carrying capacity of the DC link busbar is exceeded, two solutions are possible:
either the building of the drive group with infeed from left and right (center infeed; see below)
or the use of another Line Module.
Note
The following examples are based on the concurrent use and loading of the Motor Modules
with the rated output current of the Motor Modules. The current values are taken from the
Equipment Manual for Booksize Power Units or the NC61 catalog.
Example 1:
Connection of several Motor Modules with different current carrying capacity of the DC link
busbar to a Line Module.
Figure 2-9
Guide for the SINUMERIK 840D sl machine configuring
Manual, 07/2006 Edition, 6FC5397-6CP10-0BA0
Capacitor and Control Supply Module), the DC link busbar can be loaded with 100 A.
loaded with 200 A.
Regular construction; DC link busbars not overloaded
2.3 Current Carrying Capacity of the DC Link Busbar
Structure of the drive group
2-11