Commissioning
2.10 Commissioning of power units connected in parallel
Parallel connection of infeeds in STARTER
Figure 2-29
You need to specify the number of infeeds to be connected in parallel in the appropriate field
(maximum 4 infeeds).
Active Line Modules can also be used in the master/slave mode. The master/slave function
can be selected as option in this window (for further information, refer to the SINAMICS
S120 Function Manual, Chapter "Master/slave function for infeeds" ).
The line filter is offered as an option, depending on the infeed. An Active Interface Module
(AIM) with integrated line filter is required to operate an "Active Line Module" (ALM). We
recommend external line filters to operate the "Basic Line Module" (BLM) and "Smart Line
Module" (SLM) Line Modules.
138
Example of parallel connection of 3 Active Line Modules (chassis type)
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Commissioning Manual