Configuring/address space
4.3 Manual operation (without technology object)
Parameter
Time base for velocity
measurement
1
Increments per unit
1
Because the number of parameters is limited to a maximum of 244 bytes per station in the PROFIBUS GSD configura-
1
tion, the possible parameter assignments are limited. The parameters are preassigned default settings in the module. If
your PROFIBUS master supports the "Write/read data record" function, you can set these parameters using data rec-
ord 128.
When a GSD file is used, this diagnostic interrupt is enabled with the "Enable additional diagnostic interrupts" parameter
2
and is then not separately configurable.
When configuring with a GSD file, you determine the operating mode when you select the module name.
3
Explanation of parameters
You can find a detailed description of the parameters in function manual Counting,
Measurement and Position Detection, sections Basic parameters and Manual operation
available for download on the Internet
(http://support.automation.siemens.com/WW/view/en/59709820).
4.3.4
Address space
Address space of the technology module
Table 4- 13
Size per channel
Total size
64
Value range
1 ms
•
10 ms
•
100 ms
•
1 s
•
60 s
•
1...65535
Size of input and output addresses of the TM PosInput 2 with manual operation
Default setting
60 s
1
Inputs
16 bytes
32 bytes
Technology module TM PosInput 2 (6ES7551-1AB00-0AB0)
Parameter
Scope
reassign-
HSP for STEP 7
ment in RUN
(TIA Portal);
GSD file
Yes
Channel
Yes
Channel
Outputs
12 bytes
24 bytes
Manual, 06/2018, A5E03982218-AB