9.10 Backup test report to PC
9.11 Factory reset
9.12 Add output card (4M)
Building Technologies
Fire safety
1. Connect PC to the panel. Refer to chapter 'Connect PC to panel [➙ 95]'.
2. Open a web browser.
3. Enter web address with 'fc360.siemens.com' and press <enter>.
a 'FC360 Panel Configurator' is open.
4. Click 'Administration' tab.
5. Click 'Test report-Upload to PC'.
6. Enter a path and a file name and click 'OK'.
a The test report is stored to the PC.
7. Disconnect PC from the panel.
If the wrong country or language setting was selected during the start-up of the
panel, execute a factory reset to restart.
Refer to chapter 'Restore factory settings [➙ 94]'.
w Output card (4M) is installed correctly. Refer to chapter 'Output card (4M)
(FCA3602-Z1) [➙ 47]'.
1. Connect PC to the panel.
2. Open a web browser.
3. Enter web address with 'fc360.siemens.com' and press <enter>.
a 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to login to level 3 on panel.
5. Configure output card (4M). Refer to the document A6V10450595. See chapter
'Applicable documents [➙ 9]'.
6. Check output card (4M) function.
7. Disconnect PC from the panel.
Commissioning
Backup test report to PC
105 | 124
A6V10421795_en--_g
2016-11-18
9