Alarm messages
The following alarm messages are generated by the solar pump inverter.
Code
Fault
2036
PUMP MINIMUM
SPEED
2037
START DELAY
ACTIVE
Cause
This alarm occurs when the
speed reference calculated by
internal MPPT algorithm is less
than the pump minimum speed
set in
6006 PUMP MINIMUM
SPD.
If the pump minimum speed
alarm occurs for three
consecutive time (within time
defined in P
6019
* 5), the next
auto restart occurs after
10 minutes.
This alarm occurs when the
fault auto reset delay is active.
The drive is in standby mode
until the fault reset time is
complete.
Fault tracing 69
What to do
Check the pump minimum speed
set in
6006 PUMP MINIMUM
SPD.
Check the time set in
FAULT RESET
TIME.
6019