ABB PSTX Series Installation And Commissioning Manual page 134

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

Parameter
Description
number
08.32
Start ramp time seq 2
08.33
Start ramp init lvl seq 2
08.34
Curr lim level seq 2
08.35
Kick start seq 2
08.36
Kick start level seq 2
08
Sequence start
08.37
Kick start time seq 2
08.38
Torque limit lvl seq 2
08.39
Torque tune seq 2
08.40
Torque ctrl gain seq 2
08.60
Ie seq 3
08.61
Start mode seq 3
08.62
Start ramp time seq 3
08.63
Start ramp init lvl seq 3
08.64
Curr lim level seq 3
08.65
Kick start seq 3
08.66
Kick start level seq 3
08.67
Kick start time seq 3
08.68
Torque limit lvl seq 3
08.69
Torque tune seq 3
08.70
Torque ctrl gain seq 3
09
Automatic restart
09.01
Auto-reset delay time
7
09.02
Auto-restart
09.03
Auto-restart max attempts
10
Internal IO
10.01
In0 function
10.02
In1 function
10.03
In2 function
10.04
K4 function
10.05
K5 function
10.06
K6 function
10.07
AO reference
10.08
AO type
10.09
AO max value
10.10
AO min value
134
Functions | Installation and commissioning manual |
Setting range
1 ... 120 s
10 ... 99%
0.5 ... 7.5 x I e
On / Off
50 ... 100%
0.20 ... 2.00 s
20 ... 200%
0 ... 1000%
0.01 ... 10.00
9.0 ... 1250 A
Voltage ramp, Torque ramp, Full voltage start
1 ... 120 s
10 ... 99%
0.5 ... 7.5 x I e
On / Off
50 ... 100%
0.2 ... 2.00 s
20 ... 200%
0 ... 1000%
0.01 ... 10.0
0 ... 3600 s
On / Off
1 ... 10
None, Reset, Enable, Slow speed forward,
Slow speed reverse, Motor heating, Stand-
still brake, Start reverse, User defined
protection, Emergency mode, Fieldbus
disable control, Start 1, Start 2, Start 3. *
0 ... 15 *
0 ... 15 *
None, Run, Top of ramp, Event group 0,
Event group 1, Event group 2, Event group
3, Event group 4, Event group 5, Event
group 6,
Sequence 1 RUN, Sequence 2 RUN,
Sequence 3 RUN, Sequence 1 TOR,
Sequence 2 TOR, Sequence 3 TOR,
Run reverse **
0 ... 17 **
None, Run, Top of ramp, Event group 0,
Event group 1, Event group 2, Event group
3, Event group 4, Event group 5, Event
group 6, Sequence 1 Run, Sequence 2 Run,
Sequence 3 Run
0-10 mA, 0-20 mA, 4-20 mA, 0-10 V
Motor current [A], Mains voltage [V], Active
power [kW], Active power [HP], Reactive
power [kVAr], Apparent power [kVA], Active
energy [kWh], Reactive energy [kVArh], COS
[COS [ ], Motor temperature [%], Thyristor
temperature [%], Motor voltage [%]
0.0 ... 1000000.0
0.0 ... 1000000.0
1SFC132081M0201
Number of
Fieldbus
Default value
decimals
ID
0
203
10 s
0
204
30%
1
205
7.0 x I e
0
206
Off
0
207
70%
2
208
0.20 s
0
209
150%
0
210
100%
2
211
0.02
1
212
30 A
0
213
Voltage ramp
0
214
10 s
0
215
30%
1
216
7.0 x I e
0
217
Off
0
218
70%
2
219
0.2 s
0
220
150%
0
221
100%
2
222
0.02
0
223
10 s
0
224
Off
0
225
5
0
130
Reset
0
131
None
0
132
None
0
133
Run
0
134
Top of ramp
0
135
Event group 0
0
137
4-20 mA
0
138
Motor current
[A]
0
139
500
0
140
0
Actual
setting

Hide quick links: