Unspecified fault
7.19.1.6
Unspecified fault has these parameters:
Parameter
25.11 Unspecified fault out
25.12 Unspecified fault op
7.19.2
External faults
Phase loss fault
7.19.2.1
Voltage to 1 or more phases are missing.
For example, this senses an open line contactor.
Phase loss fault has these parameters:
Parameter
26.01 Phase loss out
26.02 Phase loss op
Bad network fault
7.19.2.2
Bad network quality fault is signaled if there is too much
frequency interference in the network. Then it is too
difficult to control the triggering of the thyristors in a safe
way.
Bad network fault has these parameters:
Parameter
26.03 Bad network out
26.04 Bad network op
Description
Identifies the Event groups this
fault is part of.
Set the operation of this fault.
Description
Identifies the Event groups this
fault is part of.
Set the operation of this fault.
Description
Identifies the Event groups this
fault is part of.
Set the operation of this fault.
1SFC132081M0201
| Installation and commissioning manual | Functions
Setting range
Default value
Eventgroup 0 .. 6
0000001
Stop manual, Stop
Stop manual
auto
Setting range
Default value
Eventgroup 0 ... 6
0000001
Stop manual, Stop
Stop manual
auto
Setting range
Default value
Eventgroup 0 ... 6
0000001
Stop manual, Stop
Stop manual
auto