Parameter Descriptions
SP-10 Line failure
Option:
3
3
SP-11 Line Voltage at Input Fault
Range:
342 V
[180 -
*
600 V]
SP-12 Function at Line Imbalance
Operation under severe main imbalance conditions reduces the
lifetime of the motor. Conditions are considered severe if the
motor is operated continuously near nominal load (e.g. a pump
or fan running near full speed).
Option:
[0]
*
[1]
[2]
SP-13 Mains Failure Step Factor
Range:
1
*
80
AF-650 GP Programming Guide
Function:
Illustration 3.39 [7] Kinetic Back-Up, trip with
recovery where mains return below SP-15 Kin.
Backup Trip Recovery Level. In this illustration a
quick ramp is used.
A
Normal Operation
B
Mains failure
C
Kinetic back-up
D
Mains return
E
Kinetic back-up ramping to trip
F
Trip
Table 3.21 Legend to Illustration 3.39
Function:
This parameter defines the threshold voltage
at which the selected function in SP-10 Line
failure should be activated. It may be
considered to choose 90% of the nominal
mains as the detection level, depending on
the supply quality. For a supply of 380 V
SP-11 Line Voltage at Input Fault should thus
be set to 342 V. This results in a DC detection
level of 462 V (SP-11 Line Voltage at Input Fault
* 1.35)
Function:
Trip
Trips the frequency
converter
Warning
Issues a warning
Disabled
No action
Function:
[0 - 5]
SP-14 Kin. Backup Time Out
Range:
Function:
60 s
[0 - 60
This parameter defines the Kinetic Backup Time
*
s]
Out in flux mode when running on low voltage
grids. If the supply voltage does not increase
above the value defined in SP-11 Line Voltage at
Input Fault +5% within the specified time, the
drive will then automatically run a controlled
ramp-down profile before stopping.
SP-15 Kin. Backup Trip Recovery Level
Range:
60000.000 Referen-
[0 - 60000.000
ceFeedbackUnit
ReferenceFeed-
*
backUnit]
3.9.2 SP-2# Reset Functions
Parameters to configure the trip delay do to Torque Limit
or Drive Fault.
SP-24 Trip Delay at Current Limit
Range:
Function:
60 s
[0 - 60
Enter the current limit trip delay in seconds.
*
s]
When the output current reaches the current
limit (F-43 Current Limit), a warning is triggered.
When the current limit warning has been contin-
uously present for the period specified in this
parameter, the frequency converter trips. Disable
the trip delay by setting the parameter to 60 s =
OFF. Thermal monitoring of the frequency
converter will still remain active.
SP-25 Trip Delay at Torque Limit
Range:
Function:
60 s
[0 - 60
Enter the torque limit trip delay in seconds.
*
s]
When the output torque reaches the torque
limits (F-40 Torque Limiter (Driving) and
F-41 Torque Limiter (Braking)), a warning is
triggered. When the torque limit warning has
been continuously present for the period
specified in this parameter, the frequency
converter trips. Disable the trip delay by setting
the parameter to 60 s = Off. Thermal monitoring
of the frequency converter will still remain active.
SP-26 Trip Delay at Drive Fault
Range:
Function:
0 s
[0 - 35 s] When the frequency converter detects an over-
*
voltage in the set time trip will be effected after
the set time.
DET-618C
Function:
This parameter
specifies the Kinetic
Backup Trip
Recovery Level. The
unit is defined in
K-02 Motor Speed
Unit.