ABB ACH580 Series User Manual page 27

E-clipse bypass and packaged drive
Table of Contents

Advertisement

18
Basic control connections for E-Clipse HVAC Default
Parameter Number
Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Smoke
Control mode which may reassign the function of the other Digital Inputs. Refer to the Smoke Control
(Override1) documentation.
Installation
ACH580 CONTROL BOARD
X1
Terminal for Signal Cable Shield
1
+
Analog Input 1
2
-
Analog Input Common
3
+10V Reference Voltage for Potentiometer
4
5
6
7
8
9
E-CLIPSE BYPASS CONTROL BOARD
X2
+24Vdc
1
+24Vdc
2
Digital Input Common
3
GND
4
Digital Input 1 (Parameter 1601)
5
Digital Input 2 (Parameter 1602,06)
6
Digital Input 3 (Parameter 1603)
7
Digital Input 4 (Parameter 1604,07)
8
Digital Input 5 (Parameter 1605, 1701) NOT SEL
9
Digital Input 6 (Fixed)
10
X2
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Parameters Changed Relative to E-Clipse HVAC Default
ACH580 E-Clipse bypass and packaged drive user manual
Analog Input 2
Analog Input Common
Analog Output 1
Analog Output 2
Analog Output Common
Relay Output 1 (parameter 1401) BYP NOT FLT
Default Operation: Bypass Not Faulted
Bypass Faulted
Relay Output 2 (parameter 1404) SYS RUNNING
Default Operation: System Running
Relay Output 3 (parameter 1407) SYS STARTED
Default Operation: System started
Relay Output 4 (parameter 1410) BYPASS SEL
Default Operation: Bypass selected
Relay Output 5 (parameter 1413) BYPASS AUTO
Default Operation: Bypass auto
Description
START/STOP
NOT SEL
START INTERLOCK 1
NOT SEL
SMOKE CONTROL*
(OVERRIDE 1)
11 connected to 13
11 connected to 12
14 connected to 16
17 connected to 19
20 connected to 22
23 connected to 25
Setting