28.5

Fuses

The power supply fuses on the Main board 5010 are as follows:
28.6

Current consumption measurement

The current consumption of FT1020G3 should be measured, an approximate value is
displayed via menu H5/A4.
To measure the actual current consumption of FT1020G3, turn off the mains power (230
and use e.g. a "clamp current meter" on one the wires between one of the batteries
V
AC
and the main board 5010. If the clamp current meter is not available, use a multimeter in
series with the same wire.
F1 = T6.3A Ceramic. +24 V DC from the power supply.
F2 = T6.3 A Ceramic. + to/from batteries
F = T6.3 A Ceramic. Between the batteries