Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

7
Periphery board (2 loops) FCI2002-A1

Technical data

7.6 Technical data
Supply input
Input
3rd supply source [FR]
Supply outputs 1 and 2
Detector line
Changeover contacts
RT fault
60
Building Technologies
Fire Safety
Designation
Operating voltage
Operating current
Designation
Voltage
Current
Designation
Voltage
Current
Designation
Output voltage
Number of integrated line cards
Output current per integrated line card
Addressable devices per integrated line card
Connectable lines per integrated line card
Protocol
Cable types
Monitored for
Design
Designation
Design
Switching voltage
Switching current
'VSYS+'; 'VSYS-'
DC 21...28.6 V (= Vsys)
Max. 5 A
'3SRC+'; '3SRC-'
DC 7...30 V
Max. 40 mA
'VSYS_01', 'VSYS_02'; 'GND'
DC 21...28.6 V
Max. 1 A (protected with 1 AT)
'LOOP1_1+'; 'LOOP1_1-' ...
LOOP2_2+'; 'LOOP2_2-'
Max. DC 33 V
1
Max. 0.5 A
Max. 252
2 loops or 4 stubs (mixed variants are
possible)
FDnet
All types (recommended: twisted); for
detailed specifications see document
008843
Ground fault
Short-circuit
Open line
Line capacitance
Short-circuit-proof
Voltage surge protection
Open line
'FAU_NO'; 'FAU_COM'; 'FAU_NC'
Relay output
Break or make contact
Failsafe
Activated in degraded mode
Max. DC 60 V
Max. 400 mA
008837_q_en_--
14.05.2012