1MRS756566
3.4.8.3.
3.4.8.4.
COM600 Station Automation Series
User's Guide

Protection activation information (ACT)

Table 3.4.8.3-1 Configurable ACT properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
ACT
Class
Addresses
General Index
-1 to 65535
Default: -1
Neutral Index
-1 to 65535
Default: -1
Phase A Index
-1 to 65535
Default: -1
Phase B Index
-1 to 65535
Default: -1
Phase C Index
-1 to 65535
Default: -1
Data Class Spe-
-1 to 65535
cific
Default: -1
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)

Analog set point (APC)

Table 3.4.8.4-1 Configurable APC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
APC
Class
Addresses
Control Index
-1 to 65535
Default: -1
LAN/WAN Master
Description
Common data class according to IEC
61850.
General Index
Phase A Index
Phase B Index
Phase C Index
Object number for indication.
Description
Common data class according to IEC
61850.
Control index.
DNP 3.0
(OPC) 3.2