ABB i-bus KNX Product Manual page 49

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
"Fault lamp" 1 bit
Options:
yes
no
Via this communication object, a fault of a lamp for the DALI output can be sent or read.
no: The communication object Fault lamp is not enabled.
yes: The communication object Fault lamp is enabled. As soon as there is a lamp fault on the
output, it is indicated by a 1 in the communication object Fault lamp. A further parameter ap-
pears:
Number of detected failures
is greater or equal
Options:
1...64
If the number of lamp faults reaches the value set here, the communication object Fault
lamp is set to 1. If the number of lamp faults is less than the value set here, the communica-
tion object Fault lamp contains the value 0.
send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
DGN/S 1.16.1 | 2CDC 507 114 D0201 47