ABB i-bus KNX Product Manual page 137

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Planning and Application
In the following table with the parameterized function Staircase lighting, the response to incoming tele-
grams is shown.
Function Staircase lighting
Operating situation
or
communication objects
Download (start)
Download (end)
Voltage
failure
KNX
Voltage
recovery
Voltage
DALI
failure
or
Gateway
Voltage
operation
recovery
ON
Switch
OFF
Relative dimming
Set brightness value
0
Function
Activate staircase
1
lighting
starts staircase lighting
Scene recall
Central commands
Central command is
switch, dimming or set
brightness via object
DALI output
1)
The parameterisation active means active standby. The lighting group has function staircase lighting and wait for an incoming trigger
signal (ON telegram via object switch).
Active
Inactive
Standby
Programmable:
Gx Fault
- Brightness value
Active and starts
Switch on value
Staircase lighting
OFF
no reaction
Dimming
Brightness value
no reaction
Goes to inactive
Activated,
Activated,
starts staircase lighting
Scene is
Scene is
executed
executed
Central command is
executed
executed
Dimming up
phase
Such as KNX voltage failure
Such as KNX voltage recovery
Programmable brightness value Gx: Fault
and staircase lighting sequence is continued from this value.
Programmable:
- Operation Gx Staircase lighting
- Brightness value: Gx Fault
Programmable:
- Brightness value Gx Fault
Programmable:
- Operation Gx Slave
- Brightness value: Gx Fault
No reaction
Goes to dimming down phase
Programmable:
- no reaction
- goes to standby and brightness value is dimmed down
Programmable:
- no reaction
- goes to standby and brightness value is set
Goes to inactive, brightness value is retained
Restarts staircase light
- goes to standby and scene is carried out
goes to standby and central command is carried out
Dimming down
phase
Holding
phase
Basis brightness
phase
is set,
1)
Holding phase
Staircase lighting
is restarted
is restarted
no reaction
Programmable:
- no reaction
DGN/S 1.16.1 | 2CDC 507 114 D0201 135