Configuring Versamax Profinet Scanner Parameters - GE PACSystems RX3i User Manual

Profinet io-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Chapter 3. Configuration
3.7.1

Configuring VersaMax PROFINET Scanner Parameters

After adding a VersaMax PNS to the LAN, its parameters can be configured by either double-clicking on the
Scanner in the Navigator, or right-clicking and selecting Configure from the menu.
3.7.1.1
PROFINET Scanner Parameters (Settings Tab)
Inputs Default: Choose whether the RX3i CPU will set inputs from any modules in the PNS module's remote
node to Off or Hold Last State in the following cases:
The PROFINET Controller is not operational or has been removed.
The PROFINET Controller cannot communicate with the scanner due to cable or network configuration
issues.
The PNS is not able to scan the I/O module in its remote node.
Input Status and Length: The address in reference memory for the 32 bits of status data associated with the
PNS. The address can be assigned to valid %G, %I, %Q, %T or %M memory or Symbolic bits. The default value is
the next available %I address. Refer to the VersaMax PROFINET Scanner Manual, GFK-2721, for definitions of
the PNS input status bits.
Output Status and Length: The address in reference memory for the 32 bits of output control data
associated with the PNS. The address can be assigned to valid %G, %I, %Q, %T or %M memory or Symbolic bits.
The default value is the next available %Q address. Refer to the VersaMax PROFINET Scanner Manual, GFK-
2721, for definitions of the PNS output control bits.
I/O Scan Set: Specifies the I/O scan set to be assigned to the PNS. Scan sets are defined in the CPU's Scan Sets
tab. The valid range is 1 through 32; the default value is 1.
66
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
Figure 54: Select PNS for Parameter Configuration
Figure 55: PNS Parameters Settings Tab
GFK-2571N