Siemens MICROMASTER 420 Operating Instructions Manual page 25

Canopen option module
Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

Issue 01/05
O-Ind
S-
Object name
Ind
.3
Third mapped
object
4.
Fourth
mapped
object
2000H
SDO-
*
>Parameter
-
Channel
2801H
*
2396H
Node ID
*
27DAH
Baudrate
*
2802H
Free Objects
*
into drive
.3
Free Object
into drive
.4
Free Object
into drive
CANopen Option Module
Operating Instructions
6SE6400-5BC00-0BP0
Description
Transf.
using
Third mapped object.
SDO
Fourth mapped
SDO
object.
Objects of the SDO
SDO
-> parameter channel
ID or address of the
SDO
MICROMASTER
Baudrate
SDO
Free objects, with
which non-defined
process data can be
sent from the
CANopen master to
the MICROMASTER
Free object which can
SDO/
be used to send non-
PDO
defined process data
to the
MICROMASTER
P2050.2
Free object which can
SDO/
be used to send non-
PDO
defined process data
to the
MICROMASTER
P2050.3
Data transfer using CANopen
D-type /
Default value / comment
access
U32 /
0H /
rw
Mapping can be changed via CANopen (can
also be set using the high byte of parameter
27F9.03 H)
U32 /
0H /
rw
Mapping can be changed via CANopen (can
also be set using the high byte of parameter
27F9.03 H)
- /
Using these objects, it is possible to access all
of the parameters in the MICROMASTER
according to the formula MICROMASTER
parameter number in hex + 2000H = SDO
number. In this case, it does not involve
CANopen objects, as the numbering of the
sub-indices differs with respect to CAN-open
(subindex 0 does not contain the number of
objects, but already the first object). However,
the objects from the parameter channel can,
just like CANopen objects, be read and written
using SDO access operations - they are
designated with a * in the following.
U16 /
These objects set the NodeID of the
rw
MICROMASTER.
If this value is changed on the CAN bus it
takes effect after a reset communication or
reset node network command.
U16 /
10 /
rw
Baud rate in kbit/s
These objects directly write process data into
parameters P2050.2, P2050.3 and P2050.5.
The gaps in the sub-indices are due to the
mirroring of the object directly to parameter
P2050 (PZD from CB). All other receive
channels of the P2050 are occupied with the
objects of the device profile. An error message
is output if an attempt is made to map other
sub-indices or to read/write using an SDO.
I16 /
0 /
rw
Values are directly written into P2050.2.
I16 /
0 /
rw
Values are directly written into P2050.3.
25