Siemens sitrans LR 400 Instruction Manual page 65

Hide thumbs Also See for sitrans LR 400:
Table of Contents

Advertisement

Note: For parameter descriptions, please refer to the associated HART parameters on
pages 27 to 56.
Parameter, menu
identification
4.2.1.1: Nozzle height = [1.3]
4.2.1.2: Tank height
4.2.1.3: Stilling pipe?
[Liquids}
If yes, 4.2.1.3.2: Pipe
diameter
[Liquids}
4.2.2: Measuring
conditions
4.2.2.1: Applic. type
4.2.2.2: Surface
4.2.2.3: Dead band
4.2.2.4: Correction
factor
4.2.2.5: Filling speed
4.2.2.6 Reflectivity
4.2.2.7: Failsafe level Selects the default mea-
4.2.2.8: Failsafe timer Sets the time delay, in
Page 62
SITRANS LR 400 (Solids) – INSTRUCTION MANUAL
Parameters (PROFIBUS PA)
Description
= [1.4]
Stilling pipe available?
Diameter (internal) of the
stilling pipe
Use of the vessel
Surface structure of the
material
Not displayed if a user
tank is selected in
[4.2.2.1].
Defines the distance from
below the flange to be
ignored by the transmit-
ter/receiver
Correction factor for
physical measuring influ-
ences. Generally only
applies to liquid applica-
tions using a stilling well.
Typical speed of change
of the level
Not displayed if a user
tank is selected in
[4.2.2.1].
For qualified personnel only
surement in the event the
failsafe timer expires
minutes, before going
into failsafe level
Factory
Setting
Setting
Possibilities
no
yes
no
100 mm
numerical value
Liquid (pro-
Liquid (store)
cess)
Liquid (process)
Silo1 (solids)
Silo2 (solids)
User tank1
User tank2
wavy
smooth
wavy
turbulent
0.35 m
numerical value,
Minimum value =
Length of the
antenna
1.0
numerical value
200 mm/min
numerical value
Hold
100 %
0 %
Hold
10 min
1 min
2 min
etc.
7ML19985JC02