Siemens SITRANS LG250 Operating Instructions Manual page 29

Guided wave radar, foundation fieldbus coax probe
Table of Contents

Advertisement

Setup - Probe length
Setup - Application - Type
of medium
Setup - Application - Ap-
plication
Setup - Application - Me-
dium, dielectric constant
PBD-51041056
With the distance units you can choose between m, mm and ft and
with the temperature units betwenn °C, °F and K.
In this menu item you can enter the probe length or have the length
determined automatically by the sensor system.
When choosing "Yes", then the probe length will be determined
automatically. When choosing "No", you can enter the probe length
manually.
In this menu item you can select which type of medium you want to
measure. You can choose between liquid or bulk solid.
In this menu item, you can select the application. You can choose
between level measurement and interface measurement. You can
also choose between measurement in a vessel or in a bypass or
standpipe.
Note:
The selection of the application has a considerable influence on all
other menu items. Keep in mind that as you continue with the param-
eter adjustment, individual menu items are only optionally available.
You have the option of choosing the demonstration mode. This mode
is only suitable for test and demonstration purposes. In this mode, the
sensor ignores the parameters of the application and reacts immedi-
ately to each change.
In this menu item, you can define the type of medium (product).
This menu item is only available if you have selected level measure-
ment under the menu item "Application".
You can choose between the following medium types:
SITRANS LG250 - Operating Instructions
29