User Programmable Elements - GE D30 Instruction Manual

Line distance protection system, ur series
Hide thumbs Also See for D30:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
LOAD ENCROACHMENT
Responds to:
Positive-sequence quantities
Minimum voltage:
0.000 to 3.000 pu in steps of 0.001
Reach (sec. Ω):
0.02 to 250.00 Ω in steps of 0.01
Impedance accuracy:
±5%
Angle:
5 to 50° in steps of 1
Angle accuracy:
±2°
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
<30 ms at 60 Hz
FLEXLOGIC
Programming language: Reverse Polish Notation with graphical
visualization (keypad programmable)
Lines of code:
512
Internal variables:
64
Supported operations:
NOT, XOR, OR (2 to 16 inputs), AND (2
to 16 inputs), NOR (2 to 16 inputs),
NAND (2 to 16 inputs), latch (reset-domi-
nant), edge detectors, timers
Inputs:
any logical variable, contact, or virtual
input
Number of timers:
32
Pickup delay:
0 to 60000 (ms, sec., min.) in steps of 1
Dropout delay:
0 to 60000 (ms, sec., min.) in steps of 1
FLEXCURVES™
Number:
4 (A through D)
Reset points:
40 (0 through 1 of pickup)
Operate points:
80 (1 through 20 of pickup)
Time delay:
0 to 65535 ms in steps of 1
FLEX STATES
Number:
up to 256 logical variables grouped
under 16 Modbus addresses
Programmability:
any logical variable, contact, or virtual
input
FLEXELEMENTS™
Number of elements:
8
Operating signal:
any analog actual value, or two values in
differential mode
Operating signal mode: signed or absolute value
Operating mode:
level, delta
Comparator direction:
over, under
Pickup Level:
–90.000 to 90.000 pu in steps of 0.001
Hysteresis:
0.1 to 50.0% in steps of 0.1
Delta dt:
20 ms to 60 days
Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001
GE Multilin
THERMAL OVERLOAD PROTECTION
Thermal overload curves: IEC 255-8 curve
Base current:
Overload (k) factor:
Trip time constant:
Reset time constant:
Minimum reset time:
Timer accuracy (cold curve): ±100 ms or 2%, whichever is greater
Timer accuracy (hot curve): ±500 ms or 2%, whichever is greater
TRIP BUS (TRIP WITHOUT FLEXLOGIC)
Number of elements:
Number of inputs:
Operate time:
Timer accuracy:
NON-VOLATILE LATCHES
Type:
Number:
Output:
Execution sequence:
USER-PROGRAMMABLE LEDs
Number:
Programmability:
Reset mode:
LED TEST
Initiation:
Number of tests:
Duration of full test:
Test sequence 1:
Test sequence 2:
Test sequence 3:
USER-DEFINABLE DISPLAYS
Number of displays:
Lines of display:
Parameters:
Invoking and scrolling:
CONTROL PUSHBUTTONS
Number of pushbuttons: 7
Operation:
D30 Line Distance Protection System
2.4 SPECIFICATIONS
0.20 to 3.00 pu in steps of 0.01
1.00 to 1.20 pu in steps of 0.05
0 to 1000 min. in steps of 1
0 to 1000 min. in steps of 1
0 to 1000 min. in steps of 1
for I
< 0.9 × k × I
and I / (k × I
p
b
6
16
<2 ms at 60 Hz
±3% or 10 ms, whichever is greater

2.4.2 USER PROGRAMMABLE ELEMENTS

set-dominant or reset-dominant
16 (individually programmed)
stored in non-volatile memory
as input prior to protection, control, and
FlexLogic
48 plus trip and alarm
from any logical variable, contact, or vir-
tual input
self-reset or latched
from any contact input or user-program-
mable condition
3, interruptible at any time
approximately 3 minutes
all LEDs on
all LEDs off, one LED at a time on for 1 s
all LEDs on, one LED at a time off for 1 s
16
2 × 20 alphanumeric characters
up to 5, any Modbus register addresses
keypad, or any user-programmable con-
dition, including pushbuttons
drive FlexLogic operands
2
) > 1.1
b
2-21