7.1 COMMANDS

PATH: COMMANDS
 COMMANDS
 CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to "Yes" and pressing the ENTER key. After clearing data, the command setting automatically reverts to "No".

PATH: COMMANDS
 COMMANDS
 SET DATE AND TIME
7
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is
over-written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
7-2

CLEAR RECORDS

CLEAR FAULT REPORTS?
No
CLEAR EVENT RECORDS?
No
CLEAR OSCILLOGRAPHY?
No
CLEAR BREAKER 1
ARCING AMPS? No
CLEAR BREAKER 2
ARCING AMPS? No
CLEAR UNAUTHORIZED
ACCESS? No
CLEAR DIRECT I/O
COUNTERS? No
CLEAR TELEPROTECT
COUNTERS? No
CLEAR ALL RELAY
RECORDS? No
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
D30 Line Distance Protection System
7 COMMANDS AND TARGETS
7.1.3 CLEAR RECORDS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes. Valid only for units with Direct Input/
Output module.
Range: No, Yes
Range: No, Yes
7.1.4 SET DATE AND TIME
(YYYY/MM/DD HH:MM:SS)