Parameter
Parameter Description
Number
P1910
Select Motor Data Identification *
0
1
2
3
NOTE
Alarm A0541 (motor data identification active) is
generated, and a measurement is made at the next ON
command.
P3900
End Quick Commissioning
0
1
2
3
The following describes the sequence of events after setting P3900 to a 1:
1.
is displayed. This means that the control data is being calculated and is then copied,
together with the parameters, from the RAM into the ROM. After quick commissioning has
been completed, P3900 is re-displayed.
NOTE
Do not disconnect from the line supply until the motor data identification has been completed and
P3900 is re-displayed. Parameter P1910 will not be saved if drive is prematurely disconnected.
2. Start motor data identification
NOTE
The motor data identification routine is started using the ON command (factory setting DIN1).
This can take several minutes depending on the size of the motor. Large motors take longer than
small motors.
Current flows through the motor and the rotor aligns itself. After motor data identification has been
completed, data is copied from the RAM into the ROM whereby
(motor data identification active) is automatically reset and P3900 is re-displayed.
3. QUICK COMMISSIONING IS NOW FINISHED.
NOTE
If you are going to run in Vector mode or Sensorless Vector mode then refer to the Operating
Instructions for further information.
MICROMASTER 440
6SE6400-5GA00-0BP0
Disabled
Identification of all parameters with parameter
change.
These are accepted and applied to the controller.
Identification of all parameters without parameter
change.
These are displayed but are not applied to the
controller.
Identification of saturation curve with parameter
change.
No quick commissioning (no motor calculations)
Motor calculation and reset all non Quick
Commissioning parameters to factory setting.
Motor calculation and reset of the I/O settings to the
factory setting.
Only motor calculation. The other parameters are not
reset.
Quick Start Guide
Suggested
User
Setting
Setting
1
1
is displayed. Alarm A0541
Issue 08/03
51