0/4 – 20mA – Current Input
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
0-20mA
P0003=3 (Expert)
P0756[0]=2 (AIN1 – Current)
P0756[1]=2 (AIN2 – Current)
Make these additional
changes for 4-20mA
P0757[0]=4 (AIN1 min 4mA)
P0757[1]=4 (AIN2 min 4mA)
P0761[0]=4 (AIN1
Deadband)
P0761[1]=4 (AIN2
Deadband)
NOTE:
Index [0] is AIN1, Index [1] is
AIN2, so if you are only
using 1 Analog Input then
you only need to change
those indices.
0 to 10V (Voltage Input)
:
Parameter Settings
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
These are the default
settings as shown. No
parameter changes are
necessary other than quick
commissioning.
MICROMASTER 440
6SE6400-5GA00-0BP0
DIP SW 1
DIP SW 2
(Analog Input 1)
(Analog Input 2)
ON (UP) = 0 to 20mA
ON (UP) = 0 to 20mA
OFF = 0 to 10V
OFF = 0 to 10V
DIP SW 1
DIP SW 2
(Analog Input 1)
(Analog Input 2)
ON (UP) = 0 to 20mA
ON (UP) = 0 to 20mA
OFF = 10V
OFF = 0 to 10V
Quick Start Guide
RL1
RL1
RL1
RL2
RL2
NC
NO
COM
NO
COM
A
A
A
OUT1
OUT1
PTC
PTC
DIN
DIN
OUT2
OUT2
+
-
A
B
5
6
+
AIN1
AIN1
DIN
DIN
DIN
DIN
10V
0V
+
-
1
2
3
0 – 20mA or
4 – 20mA
RL1
RL1
RL1
RL2
NC
NO
COM
NO
A
A
A
OUT1
OUT1
PTC
PTC
DIN
DIN
OUT2
+
-
A
B
5
6
+
AIN1
AIN1
DIN
DIN
DIN
10V
0V
+
-
1
2
3
≥ 4.7k Ω
Issue 08/03
RL3
RL3
RL3
NC
NO
COM
A
Iso
P
N
-
0V
+
-
Iso
AIN2
AIN2
4
24V
+
-
0 – 20mA or
4 – 20mA
RL2
RL3
RL3
RL3
COM
NC
NO
COM
A
Iso
OUT2
P
N
-
0V
+
-
DIN
Iso
AIN2
AIN2
4
24V
+
-
≥ 4.7k Ω
39