DNP DEVICE PROFILE
Object 80 (internal indications)
DNP protocol settings
208
–
21 (disable unsolicited response)
–
22 (assign class)
•
Qualifier codes for requests, object 60, variation 0:
–
06 (no range, or all)
There are no codes used for responses.
Object 60, variation 1: class 0 data
The following codes are used for requests.
•
Function codes for requests, object 60, variation 1:
–
1 (read)
–
22 (assign class)
•
Qualifier codes for requests, object 60, variation 1:
–
06 (no range, or all)
There are no codes used for responses.
Object 60, variation 2: class 1 data
Object 60, variation 3: class 2 data
Object 60, variation 4: class 3 data
The following codes are used for requests.
•
Function codes for requests, object 60, variation 1:
–
1 (read)
–
20 (enable unsolicited response)
–
21 (disable unsolicited response)
–
22 (assign class)
•
Qualifier codes for requests, object 60, variation 1:
–
06 (no range, or all)
–
07, 08 (limited quantity)
There are no codes used for responses.
Object 80, variation 1: internal indications
The following codes are used for requests.
•
Function codes for requests, object 80, variation 1:
–
1 (read)
•
Qualifier codes for requests, object 80, variation 1:
–
00, 01 (start-stop), index = 7
The following codes are used for responses.
•
Function codes for responses, object 80, variation 1:
–
129 (response)
•
Qualifier codes for responses, object 80, variation 1:
–
00, 01 (start-stop)
The DNP server can simultaneously support one client over serial RS485 and one client
over Ethernet or two clients over Ethernet. Level 3 is supported for parsing requests and
generating responses. It is capable of reporting any indication or measurement and
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 3: DNP COMMUNICATION