F620
Cooling Fan Control
Program  Protection
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Run-Time Alarm Setting
Program  Protection
This parameter sets a run-time value that, once exceeded, closes a discrete output
contact. The output signal may be used to control external equipment or used to
engage a brake.
Associate the Total-Operation-Hours Alarm setting of
discrete output contactor.
Note:
The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Abnormal Speed Time
Program  Protection
This parameter sets the time that an overspeed condition (speed drifts outside of
the
F623
and
F624
range) must exist to cause a trip.
This parameter functions in conjunction with the settings of
Abnormal Speed Upper Band
Program  Protection
This parameter sets the upper level of the Abnormal Speed range that, once
exceeded, will cause an Overspeed Detected alert.
This parameter functions in conjunction with the settings of
Abnormal Speed Lower Band
Program  Protection
This parameter sets the lower level of the Abnormal Speed range that, once the
output speed falls below this setting, will cause a Speed Drop Detected alert.
This parameter functions in conjunction with the settings of
134
Table 7 on pg. 190
to a
F623
and F624.
F622
and F624.
F622
and F623.
Q9 ASD Installation and Operation Manual
Direct Access Number — F620
Parameter Type — Selection List
Factory Default — Automatic
Changeable During Run — Yes
Direct Access Number — F621
Parameter Type — Numerical
Factory Default — 610.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 999.9
Units — Hours (X 10)
Direct Access Number — F622
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.00
Units — Seconds
Direct Access Number — F623
Parameter Type — Numerical
Factory Default — 0.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.0 (Disabled)
Maximum — 30.00
Units — Hz
Direct Access Number — F624
Parameter Type — Numerical
Factory Default — 0.00 (Disabled)
Changeable During Run — Yes
Minimum — 0.00 (Disabled)
Maximum — 30.00
Units — Hz