F260
Jog Run Frequency
Program  Frequency Settings
This parameter sets the output frequency of the drive during a Jog. Jog is the term
used to describe turning on the motor for discrete increments of time and may be
required when precise positioning of motor-driven equipment is required.
The Jog function may be initiated from the Terminal Board or using
Communications (for more information on using Communications for Jogging,
see the Communications manual P/N 53840).
The Jog function can be activated from zero Hz or from any frequency below the
Jog Run Frequency setting (Jog can only increase the speed). A Jog command
will not be recognized when the running frequency is above the Jog Run
Frequency setting. The Jog command has priority over other Run commands and
is not limited by the Upper-Limit setting of parameter F012.
Jog commands received for the opposite direction of the commanded frequency
will follow the programmed stopping method of
will then ramp to the programmed Jog Frequency and direction.
Jog Setup and Execution
To initiate a Jog Run from the EOI perform the following:
1.
Set the Command Mode Selection (F003) to Panel Keypad. This setting
places the ASD in the Remote mode.
2.
Set the Frequency Mode Selection (F004) to Panel Keypad.
3.
Enable the Jog function (F262).
4.
Set the Input Terminal Priority (F106) function to Enable to receive Jog
commands.
5.
Assign the Jog Run setting to any unused discrete input terminal (Select from
Table 4 on pg.
186).
6.
Set the Jog Frequency at F260.
7.
Set up a Jog Stop Pattern at F261.
8.
Press the Run key and the ASD will output the commanded frequency (as
programmed; not the Jog frequency).
9.
Activate the Jog Run terminal (from step 5). The ASD will output the
frequency setting of
F260
10. Stop the Jog by either providing a Stop command, or by terminating the Jog
Run terminal activation. Providing a Stop command will terminate the
commanded frequency and the Jog function. Terminating the Jog Run
terminal activation will terminate the Jog function only and will resume the
commanded frequency of step 8.
Q9 ASD Installation and Operation Manual
F261
until reaching zero Hz and
(from step 6).
Direct Access Number — F260
Parameter Type — Numerical
Factory Default — 5.00
Changeable During Run — Yes
Minimum —
F240
Setting
Maximum — 20.00
Units — Hz
F260
101