GE MI-869 Instruction Manual page 450

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

CONTROL
4–332
START TIMER
Range: 1.0 to 600.0 s in steps of 0.1
Default: 10.0 s
BLOCK
Range: Off, Any FlexLogic Operand
Default: Off
TRIP OUTPUT RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Reduced Volt Fail.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-Reset, Latched
Default: Latched
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS