GE MI-869 Instruction Manual page 258

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

PROTECTION
4–140
BLOCK
Range: FlexLogic Operand
Default: Off
The mechanical jam can be blocked by any asserted FlexLogic operand.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Mechanical Jam operation.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Disabled
Default: Latched
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS

Advertisement

Table of Contents
loading

This manual is also suitable for:

869

Table of Contents