System Setup Requirements - Toshiba Q9 Installation And Operation Manual

Flowsaver/bypass low voltage variable torque hvac inverter
Table of Contents

Advertisement

DO NOT allow personnel near rotating machinery. Warning signs to this effect shall be posted at or
near the machinery.
DO NOT allow personnel near electrical conductors. Human contact with electrical conductors can
be fatal. Warning signs to this effect shall be posted at or near the hazard.
Personal protection equipment shall be provided and used to protect employees from any hazards
inherent to system operation.

System Setup Requirements

When using the Q9 F
Q9 F
arrangement designed to switch the system to a safe condition if there is a fault or failure).
System safety features should be employed and designed into the integrated system in a manner
such that system operation, even in the event of system failure, will not cause harm or result in
personnel injury or system damage (i.e., E-Off, Auto-Restart settings, System Interlocks, etc.).
The programming setup and system configuration of the Q9 F
motor unexpectedly. A familiarity with the Auto-restart settings is a requirement to use this
product.
Improperly designed or improperly installed system interlocks may render the motor unable to start
or stop on command.
The failure of external or ancillary components may cause intermittent system operation (i.e., the
system may start the motor without warning).
There may be thermal or physical properties, or ancillary devices integrated into the overall system
that may allow for the Q9 F
installation must be posted to this effect.
If a secondary magnetic contactor (MC) is used between the ASD and the load, it should be
interlocked to halt the ASD before the secondary contact opens. If the output contactor is used for
bypass operation, it must be interlocked such that commercial power is never applied to the ASD
output terminals (T1, T2, T3).
Power factor improvement capacitors or surge absorbers MUST NOT BE INSTALLED on the
output of the Q9 F
Use of the built-in system protective features is highly recommended (i.e., E-Off, Overload
Protection, etc.).
The operating controls and system status indicators should be clearly readable and positioned
where the operator can see them without obstruction.
The Dynamic Braking function is not used with the Q9 ASD.
DO NOT attempt to configure or connect the DBR function to the Q9 ASD.
Attempts to configure or adapt the Q9 ASD to use the Dynamic Braking function may result in
system damage or injury to personnel.
Additional warnings and notifications shall be posted at the equipment installation location as
deemed required by Qualified Personnel.
Follow all warnings and precautions and do not exceed equipment ratings.
Q9 FlowSaver Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
S
as an integral part of a larger system, it is the responsibility of the
LOW
AVER
S
installer or maintenance personnel to ensure that there is a fail-safe in place (i.e., an
LOW
AVER
S
LOW
S
.
LOW
AVER
to start the motor without warning. Signs at the equipment
AVER
S
may allow it to start the
LOW
AVER
7