Siemens 7SG11 Manual page 96

Hide thumbs Also See for 7SG11:
Table of Contents

Advertisement

Setting name
Gn P/F [E/F][SEF] Reclose DTL
2
Gn P/F [E/F][SEF] Protection
Trip 3
Gn P/F [E/F][SEF] Reclose DTL
3
Gn P/F [E/F][SEF] Protection
Trip 4
Gn P/F [E/F][SEF] Reclose DTL
4
Gn P/F [E/F][SEF] Shots To
Lockout
Gn P/F [E/F] HS1 Trips to
Lockout
Gn P/F [E/F] HS2 Trips to
Lockout
Reclaim Time
Close Pulse
Manual Close Delay
LO Recovery
©2013 Siemens Protection Devices Limited
Range (bold = default)
as Reclose DTL 1
INST, DELAYED
as Reclose DTL 1
INST, DELAYED
as Reclose DTL 1
1, 2, 3, 4
1, 2, 3, 4, 5
1, 2, 3, 4, 5
0.20, 0.21...2.0, 2.1...20,21...
300, 360...3600, 3900...14400
1.0, 1.1...2.0...10.0
OFF, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10
as 'Reclaim Time'
7SG11 Argus Technical Reference
Units Notes
sec
sec
sec
For 4 reclose shots, 5 trips are
issued – the fifth trip is always
delayed.
Not applicable to SEF sequence
Common setting across all
Groups
sec
applies to all Sequences
Common setting across all
sec
Groups
Common setting across all
sec
Groups
Common setting across all
sec
Groups
P20007 Page 41 of 71