Test Instructions For Fap-425-Dotc-R / Fap-425-Dot-R / Fap-425-Ot-R / Fap-425-Ot; Diagnostic Data - Bosch AVENAR FAP-425 Operation Manual

Detector 4000
Table of Contents

Advertisement

32
en | Maintenance and Service
7.2.2
Test Instructions for FAP‑425‑DOTC‑R / FAP‑425‑DOT‑R / FAP‑425‑OT‑R /
FAP‑425‑OT
Sequential walktest
Select walktest type "Sequential walktest" on the FPA-5000/FPA-1200 panel controller in the
walktest menu.
Notice!
The test head must remain over the detector until the detector has been triggered. The time
taken to distribute the test aerosol in the test head and therefore the trigger time of the
sensor can be up to 20 seconds.
Simultaneous walktest
Select walktest type "Simultaneous Walktest" on the the FPA-5000/FPA-1200 panel controller
in the walktest menu.
Multisensor detectors can be tested simultaneously with the FME-TESTIFIRE multi-stimulus
test tool. Observe the notes in the detector testing device and fire panel operating
instructions.
Notice!
An alarm message is only displayed on the panel if all sensors are triggered during the
simultaneous walktest. If this does not happen, one of the sensors is faulty.
Testing outside the Revision Mode
The FAP-425-DOTC-R detector can be triggered outisde of the revision mode only by the
following stimuli:
7.3

Diagnostic Data

Module where the detector or detector line is installed.
Detector installation address, e.g. 10-03: The detector is in zone 10 and is the detector
number 3.
Additional information entered during programming. You can also enter the position of the
detector here.
Detector type
2014.11 | 1.1 | F.01U.283.550
The same test device is used to test the CO sensor in the FAP-425-DOTC-R. You only need
to exchange the test aerosol with the CO testing gas bottle. The testing gas must be
applied for 1/2 to 1 second for the CO test.
The thermal sensor of the FAP-425-DOTC-R / FAP-425-DOT-R / FAP-425-OT-R / FAP-425-
OT is tested with the test device for heat detectors.
Rise of temperature according to the sensitivity settings A2R, A2S, BR, and BS as defined
by EN 54-5
Simultaneous creation of artificial smoke and CO (by a suitable multi-stimulus test tool,
like FME-TESTIFIRE)
Simultaneous creation of artificial smoke and rise of temperature (by a suitable multi-
stimulus test tool, like FME-TESTIFIRE)
Module Address
Address
Brief Info
Type
Serial number
Operation Guide