11/03
4.9.8

EMERGENCY OFF Category 1; 230 V AC (Option L59)

Description
EMERGENCY OFF category 1 for controlled stop to EN 60 204. This function
involves stopping the drive by means of a rapid stop using a deceleration ramp that
can be parameterized by the user. The cabinet unit is then disconnected from the
supply via the line contactor bypassing the electronics by means of a safety
combination to EN 60 204-1. A braking unit may be necessary to achieve the
required shutdown times.
The operational status is indicated by a total of eight LEDs.
Connection
Table 4-23
AC)
Terminal
7
8
15
16
17
18
Max. connectable cross-section: 4 mm² (AWG 10)
Setting
When the emergency stop function (OFF3 ramp-down time, p1135) is used to shut
down the drive, the ramp-down time should be less than (or at the most equal to)
the time set on the contactor combination, after which the converter is de-
energized.
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs) are
described in "Additional Operating Instructions" in the operating manual.
SINAMICS G150
Operating Manual
Terminal block X120 – connection for EMERGENCY OFF category 1 (230 V
Loop in EMERGENCY OFF button from system side,
remove jumper 15–16 and connect button
Checkback "trip safety combination"
Technical data
remove jumper 7-8
"On" for monitored start:
Electrical Installation
4-31