Discrete Inputs (1xxxx) – Function code 02: Read Discrete Input
Address
Description
10X01
upsAlarmBatteryBad
10X02
upsAlarmOnBattery
10X03
upsAlarmLowBattery
10X04
upsAlarmDepletedBattery
10X05
upsAlarmTempBad
10X06
upsAlarmInputBad
10X07
upsAlarmOutputBad
10X08
upsAlarmOutputOverload
10X09
upsAlarmOnBypass
10X10
upsAlarmBypassBad
10X11
upsAlarmOutputOffAsRequested
10X12
upsAlarmUpsOffAsRequested
10X13
upsAlarmChargerFailed
10X14
upsAlarmUpsOutputOff
10X15
upsAlarmUpsSystemOff
10X16
upsAlarmFanFailure
10X17
upsAlarmFuseFailure
10X18
upsAlarmGeneralFault
10X19
upsAlarmDiagnosticTestFailed
10X20
upsAlarmCommunicationsLost
10X21
upsAlarmAwaitingPower
10X22
upsAlarmShutdownPending
10X23
upsAlarmShutdownImminent
10X24
upsAlarmTestInProgress
10X25
upsAlarmReceptacleOff
10X26
VoltageOnOutput (1-ph only)
upsAlarmHighSpeedBusFailure
(3-ph only)
10X27
DCLinkVoltageBad (1-ph only)
upsAlarmHighSpeedBusJACRCFailure
(3-ph only)
10X28
InputCircuitFailure (1-ph only)
upsAlarmConnectivityBusFailure
(3-ph only)
10X29
ChargeConverterError (1-ph only)
upsAlarmHighSpeedBusJBCRCFailure
(3-ph only)
10X30
BypassDefect (1-ph only)
UpsAlarmCurrentSharing (3-ph only)
10X31
PhaseNeutralReversal (1-ph only)
UpsAlarmDCRipple (3-ph only)
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Notes
One or more batteries have been determined to require
replacement.
The UPS is drawing power from the batteries.
The remaining battery run-time is less than or equal to
upsConfigLowBattTime.
The UPS will be unable to sustain the present load when
and if the utility power is lost.
A temperature is out of tolerance.
An input condition is out of tolerance.
An output condition (other than OutputOverload) is out of
tolerance.
The output load exceeds the UPS output capacity.
The Bypass is presently engaged on the UPS.
The Bypass is out of tolerance.
The UPS has shutdown as requested, i.e., the output is off.
The entire UPS has shutdown as commanded.
An uncorrected problem has been detected within the UPS
charger subsystem.
The output of the UPS is in the off state.
The UPS system is in the off state.
The failure of one or more UPS fans has been detected.
The failure of one or more fuses has been detected.
A general fault in the UPS has been detected.
The result of the last diagnostic test indicates a failure.
A problem has been encountered in the communications
between the agent and the UPS.
The UPS output is off and the UPS is awaiting the return of
input power.
A Shutdown countdown is underway.
The UPS will turn off power to the load in less than 5
seconds; this may be either a timed shutdown or a low
battery shutdown.
A test is in progress.
One or more receptacles are switched off.
A voltage has been detected on output in a unforeseen
situation
A problem on the High Speed Bus communication is
detected
The DC Link Voltage reached a high level.
A CRC problem on the Highspeed Bus JA is detected.
ByBf micro processor, IC converter, BF relay or charger is
defect.
A problem on the Connectivity Bus communication is
detected
Charge converter or DC Capacitors are defect.
A CRC problem on the Highspeed Bus JB is detected.
Bypass is not able to hold Output Voltage.
The System detects an high current sharing on the parallel
system.
There is a voltage between ground and neutral (input
reversed).
The System detects an high ripple voltage on one DC link.