Planning Instructions Fire alarm system EBL512 G3, V1.1.x
23
Routing equipment output (Fire brigade tx) is disabled.
24
The specified zone is disabled.
25
The specified alarm point (zone/address) is disabled.
26
One or more alarm points (zone/address) are disabled.
27
One or more faults are generated in the system.
28
Loss of mains (in a c.i.e. or external power supply 3366).
NOTE! The output(s) will be activated immediately but
the corresponding fault is normally delayed (set via
WinG3).
29
This control expression is true for 5 seconds, whenever a
reset pulse is sent to the specified zone/address. The
control expression can only be used in the same c.i.e. as
the specified zone/address.
30
The programmed time channel (1-63) is activated.
31
Alert annunciation activated (by any alarm point set to
activate this function).
EBL512 G3 Operating Instructions MEW01163.
32
Alert annunciation activated (by any alarm point set to
activate this function)
information, see EBL512 G3 Operating Instructions
MEW01163.
33
Door open in any control unit in the system.
34
General Key cabinet alarm activated.
information, see EBL512 G3 Operating Instructions
MEW01163.
35
This control expression is true when all control outputs of
the types Control, Fire ventilation and Extinguishing in
all control units are disabled via menu H2/B7.
output shall be type Control – neutral.
36
This control expression is true when all control outputs of
type Alarm device are disabled via menu H2/B8
output shall be type Control – neutral.
37
This trigger condition plus the OR operator shall be used
for each detector (zone-address) controlling a fire door
(normally > two detectors). Type of output is normally
71
Indicated by LED Routing equipment "Fault tx activated". Output can be
tested via menu H1.
72
Indicated by LED Fault/Disablements "Fire brigade tx".
73
Indicated by LED Fault / Disablements "General fault" and/or LED
Routing equipment "Fault tx activated".
74
Valid until the AA alarm is reset or becomes a normal fire alarm.
75
Or ext FBPs connected to the control unit(s).
Indicated by the "Door open" symbol in the display symbol area.
76
Indicated by LED Fault / Disablements "General Disablements".
77
Indicated by LED Fault / Disablements "Alarm devices".
74
For more information, see
74
and acknowledged. For more
79
72
76
73
75
For more
76
This
77
. This