Plant Synchronization Via Point-To-Point Connection - Siemens SICLOCK TC 400 Operating Instructions Manual

Plant central clock
Table of Contents

Advertisement

2.3.2

Plant synchronization via point-to-point connection

Non-networked plant equipment is synchronized via OUTPUTs 1 to 3 (point-to-
point connections). They can be parameterized independently.
OUTPUTs 1 and 2
• Current signal: 20 mA active, floating
or
• Voltage signal: 24 V, floating
OUTPUT 3
RS422, floating
Output signal
• DCF77 with local time, invertible
• DCF77 with UTC, invertible
• Pulse per second, invertible
• Pulse per minute, invertible
• Serial telegram (parameterizable output telegram, see below)
Output telegram (setting applies to all three outputs)
• Meinberg compatible (including time zones)
• Meinberg compatible (not including time zones)
• NMEA (0183/ZDA)
© Siemens AG 2007 All Rights Reserved
®
SICLOCK
TC 400
Description
2-15