Run Command Source Monitor (–Xfu2 Models Only) - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

4–50
Using Intelligent Output Terminals
Run Command
Source Monitor
(–xFU2 models
only)
The Run Command Source Monitor intelligent output provides a way to monitor the present
setting for the Run Command Source Setting parameter (A002). Some applications use devices
external to the inverter, such as intelligent keypads or network control hosts, which can change
the A002 parameter setting at various times in normal operation. In the control environment of
the inverter, a Hand/Auto or Manual/Auto mode change requires writing a new A002 setting.
So, the intelligent output Run Command Source Monitor provides a way for external devices to
know whether the inverter's Run command source is the operator keypad (A002=02), or some
other source (A002=01, 03, 04, or 05).
Opt.
Symbol
Function Name
Code
27
RMD
Run command
source monitor
11, 12, AL0 – AL2
Valid for
outputs:
A002
Required
settings:
Notes:
• This function is available only on –xFU2
models.
• The Run Command Source Monitor output
can serve as a Hand/Auto or Manual/Auto
input to a building automation system.
• To ensure safe inverter operation in
networked applications, you cannot change
an intelligent terminal assignment to/from
[RMD] (option code 27) via the network.
However, you can still read an [RMD] output
assignment over the network.
Output
Description
State
ON
when the Run command source is the
operator keypad (A002=02)
OFF
when the Run command source is not the
operator keypad (A002=01, 03, 04, or 05)
Example: (Requires output configuration—
see page 3–48.)
Inverter output terminal circuit
12C
12A
24VDC
See I/O specs on page 4–8.
RMD
11C
11A
+
L