Dell 3750W User Manual page 44

Online rack ups 3750w and 4200w
Hide thumbs Also See for 3750W:
Table of Contents

Advertisement

Table 6. Settings (continued)
Description
Bypass Voltage Low Limit
Bypass Voltage High Limit
Qualify Bypass
Synchronization Window
|
44
Operation
Available Settings
[-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is below the nominal output
voltage (-15%).
The Qualify Bypass setting may overrule the
NOTE:
Bypass Voltage Low Limit setting.
[+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is above the nominal output
voltage (+10%).
The Qualify Bypass setting may overrule the
NOTE:
Bypass Voltage High Limit setting.
[Always] [Never] [Bypass Disabled]
If Always, Bypass operation is allowed when:
S Bypass voltages > the value set for Bypass
Voltage Low Limit
S Bypass voltages < the value set for Bypass
Voltage High Limit
S Bypass frequency > (nominal frequency -3 Hz)
S Bypass frequency < (nominal frequency +3 Hz)
S Inverter is synchronized with Bypass when
unsynchronized transfers are disabled by the
value set for Unsynchronized Transfers
If Never, Bypass operation is always allowed; voltage
and frequency limits are not in use.
If Bypass Disabled, Bypass operation is prohibited.
[Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz]
[±2.0 Hz] [±2.5 Hz] [±3.0 Hz]
If ±3.0 Hz, on inverter operation the inverter tries to
synchronize with the Bypass when the Bypass
frequency is not more than 3 Hz from the nominal
output frequency; otherwise, the inverter goes to
nominal frequency. On Bypass mode, the sync
window is always ±3 Hz.
In Sync Disabled state, if the Bypass
NOTE:
operation is allowed, the UPS synchronizes only
when it is operating on Bypass mode.
Default Setting
-15% of nominal
+10% of nominal
Always
±3.0 Hz