Accessories; General Specification; Selecting Circuit Breaker And Wiring; Selecting The Pipe Material - Fujitsu KGT Series Installation Manual

Table of Contents

Advertisement

Tool name
Pressure is high and cannot be measured with a conventional
Gauge manifold
(R22) gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa (-1
to 53 bar) for high pressure. -0.1 to 3.8 MPa (-1 to 38 bar) for
low pressure.
To increase pressure resistance, the hose material and base
Charge hose
size were changed. (R32/R410A)
A conventional vacuum pump can be used by installing a
Vacuum pump
vacuum pump adapter.
(Use of a vacuum pump with a series motor is prohibited.)
Gas leakage detector
Special gas leakage detector for HFC refrigerant R32/R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of
residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed,
deformed or discolored portion (especially on the interior surface). Otherwise, the
expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R32(R410A) incurs pressure higher than when using
conventional refrigerant, it is necessary to choose adequate materials.

2.2. Accessories

For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts. The use of non-prescribed parts can cause serious accidents
such as the unit falling, water leakage, electric shock, or fi re.
• The following installation parts are supplied. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Name and shape
Installation Manual
Drain pipe

3. GENERAL SPECIFICATION

3.1. Selecting circuit breaker and wiring

Be sure to install a breaker of the specifi ed capacity.
Regulation of cables and breaker differs from each locality, refer in accordance with
local rules.
Voltage rating
Operating range
Cable
Conductor size [mm²]
Power Supply Cable
1.5
Connection Cable
1.5
*1
Selected sample: Select the correct cable type and size according to the country or
region's regulations.
* Limit the voltage drop less than 2 %. Increase the cable diameter if voltage drop is 2 %
or more.
Breaker capacity
[A]
15
• Select the breaker that enough load current can pass through it.
• Before starting work check that power is not being supplied to all poles of the indoor
unit and outdoor unit.
• Install all electrical works in accordance to standard.
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby
the units. (Both indoor unit and outdoor unit)
Contents of change
WARNING
Q'ty
Description
This manual
1
For outdoor unit drain piping work
(May not be supplied, depending on
1
the model.)
CAUTION
1 Φ 230 V (50 Hz)
198 to 264 V
*1
Type
Remarks
2 wire + Ground
Type60245 IEC57
1 Φ 230 V
3 wire + Ground
Type60245 IEC57
1 Φ 230 V
Earth leakage breaker
[mA]
30

3.2. Selecting the pipe material

Do not use existing pipes.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material: Phosphor deoxidized seamless copper pipes.
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion
(especially on the interior surface). Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using
R32(R410A) incurs pressure higher than when using conventional refrigerant, it is
necessary to choose adequate materials.
• Thicknesses of copper pipes used with R32(R410A) are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are
available on the market.
Thicknesses of Annealed Copper Pipes
Pipe outside diameter [mm (in.)]
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
19.05 (3/4)

3.3. Protection of pipes

• Protect the pipes to prevent the entry of moisture and dust.
• Especially, pay attention when passing the pipes through a hole or connecting the
end of a pipe to the outdoor unit.
Location
Working period
1 month or more
Outdoor
Less than 1 month
Indoor
-

3.4. Refrigerant pipe size and allowable piping length

Keep the piping length between the indoor unit and outdoor unit within the allowable
tolerance.
The maximum lengths of this product are shown in the table. If the units are further
apart than this, correct operation cannot be guaranteed.
Pipe diameter <Liquid/Gas> [mm (in.)]
Max. piping length (L)
[m]
Max. height difference (H)
<Indoor unit to outdoor unit>
[m]
View (Example)
CAUTION
Thickness [mm]
0.80
0.80
0.80
1.00
1.20
Protection method
Pinch pipes
Pinch or tape pipes
Pinch or tape pipes
CAUTION
6.35 (1/4) / 9.52 (3/8)
20
15
L
H
En-4