Huawei NetCol5000-A050 User Manual page 156

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Tab
System
Optional
Parts
System
Settings
Issue 13 (2023-08-20)
Parameter
Number of running
systems in this group
Cold aisle sensor
Hot aisle sensor
Cold aisle
temperature and
humidity sharing
Hot aisle temperature
and humidity sharing
Low temperature
component
Outdoor unit
condensate mode
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
Specifies the number of running units in
this group. The value is an integer
ranging from 1 to the value of Number
of systems in this group.
NOTE
This parameter is displayed after Teamwork
function is set to Enable.
Enables or disables a sensor.
Enables or disables a sensor.
This function can be enabled only when
at least one smart cooling product in
the teamwork group is equipped with
cold aisle T/H sensors. If this function is
enabled, the master unit in the
teamwork group collects the cold aisle
temperature and humidity values from
all units equipped with cold aisle
sensors, and synchronizes the
temperature and humidity control type
and setpoints to all slave units.
This function can be enabled only when
at least one smart cooling product in
the group is equipped with hot aisle T/H
sensors. If this function is enabled, the
master unit in the teamwork group
collects the hot aisle temperature and
humidity values from all units equipped
with hot aisle sensors, and synchronizes
the temperature and humidity control
type and setpoints to all slave units.
Specifies whether a low temperature
component is used.
● Air-cooled: The outdoor unit is an air-
cooled outdoor unit.
● Water-cooled: The outdoor unit is a
water-cooled module.
145