3. Indoor Unit Installation
DANGER
!
•
Check to ensure that the accessories are packed with the indoor unit.
•
Do not install the indoor units outdoors. If installed outdoors, an electric hazard or electric leakage will
occur.
•
Consider the air distribution from each indoor unit to the space of the room, and select a suitable
location so that uniform air temperature in the room can be obtained. The unit must not be installed
below 2.5 meters from the floor level, with a recommend installation height between 2.5 and 3 meters.
If the unit is installed higher than 3 meters, it is also recommended that a fan be utilized to obtain
uniform air temperature in the room.
•
Avoid obstacles which may hamper the air intake or the air discharge flow.
•
Pay attention to the following points when the indoor units are installed in a hospital or other places
where there are electronic waves from medical equipment, etc.
•
Do not install the indoor units where electromagnetic wave is directly radiated to the electrical box,
remote control cable or remote control switch.
•
Prepare a steel box and install the remote control switch in it. Prepare a steel conduit tube and wire the
remote control cable in it. Then connect the ground wire with the box and tube.
•
Install a noise filter when the power supply emits harmful noises.
•
This unit is exclusive nonelectrical heater type indoor unit. It is prohibited to install an electrical heater
in the field.
•
Do not put any foreign material into the indoor unit and check to ensure that none exist in the indoor
unit before the installation and test running. Otherwise, a fire or failure, etc., may occur.
CAUTION
!
•
Do not install the indoor units in a flammable environment to avoid a fire or an explosion.
•
Do not install the indoor unit in the laundry.
10
14
12
11
13
19
18
20
40
Item.
Fan
1
Unit : mm
Fan Motor
2
Heat Exchanger
3
Distributor
4
Strainer
5
Protective Cover(PCI(4.0-6.5) only)
6
Electrical Box
7
Refrigerant Gas Pipe Connection
8
Refrigerant Liquid Pipe Connection
9
10
Drain Pipe Connection
11
Drain Discharge Mechanism
Float Switch
2
12
Drain Pan
13
Rubber Plug for Drain
14
1
Air Panel PHKF160PAQ1
15
Air Inlet Grille
16
Air Filter
17
Air Outlet
18
Air Inlet
19
C
Cover for Corner Pocket
20
PCI(2.0-3.0):238
C
-10-
2. Name of Parts
Part Name
PCI(4.0-6.5):288