Name Of Parts; Indoor Unit Installation - Hitachi AirCore 700 Operation Installation Maintenance Manual

Single split inverter series indoor unit
Table of Contents

Advertisement

2. Name of Parts

8
9
6
5
4
3
7
15
17
16
950

3. Indoor Unit Installation

DANGER
!
Check to ensure that the accessories are packed with the indoor unit.
Do not install the indoor units outdoors. If installed outdoors, an electric hazard or electric leakage will
occur.
Consider the air distribution from each indoor unit to the space of the room, and select a suitable
location so that uniform air temperature in the room can be obtained. The unit must not be installed
below 2.5 meters from the floor level, with a recommend installation height between 2.5 and 3 meters.
If the unit is installed higher than 3 meters, it is also recommended that a fan be utilized to obtain
uniform air temperature in the room.
Avoid obstacles which may hamper the air intake or the air discharge flow.
Pay attention to the following points when the indoor units are installed in a hospital or other places
where there are electronic waves from medical equipment, etc.
Do not install the indoor units where electromagnetic wave is directly radiated to the electrical box,
remote control cable or remote control switch.
Prepare a steel box and install the remote control switch in it. Prepare a steel conduit tube and wire the
remote control cable in it. Then connect the ground wire with the box and tube.
Install a noise filter when the power supply emits harmful noises.
This unit is exclusive nonelectrical heater type indoor unit. It is prohibited to install an electrical heater
in the field.
Do not put any foreign material into the indoor unit and check to ensure that none exist in the indoor
unit before the installation and test running. Otherwise, a fire or failure, etc., may occur.
CAUTION
!
Do not install the indoor units in a flammable environment to avoid a fire or an explosion.
Do not install the indoor unit in the laundry.
10
14
12
11
13
19
18
20
40
Item.
Fan
1
Unit : mm
Fan Motor
2
Heat Exchanger
3
Distributor
4
Strainer
5
Protective Cover(PCI(4.0-6.5) only)
6
Electrical Box
7
Refrigerant Gas Pipe Connection
8
Refrigerant Liquid Pipe Connection
9
10
Drain Pipe Connection
11
Drain Discharge Mechanism
Float Switch
2
12
Drain Pan
13
Rubber Plug for Drain
14
1
Air Panel PHKF160PAQ1
15
Air Inlet Grille
16
Air Filter
17
Air Outlet
18
Air Inlet
19
C
Cover for Corner Pocket
20
PCI(2.0-3.0):238
C
-10-
2. Name of Parts
Part Name
PCI(4.0-6.5):288

Advertisement

Table of Contents
loading

Table of Contents