Tank thermistor
1 Connect the extension cable to the factory supplied cable.
1.1)
(Factory supplied cable)
(*)
1.2)
(Factory supplied cable)
(*): Use a crimping tool to crimp the cables.
2 Follow the same procedure as for the electrical heater wire
but connecting the Tank thermistor wires to the 28 and 29 con-
nections of the Terminal Board 2.
(Extension cable)
LCD controller
1 Connect the extension cable to the factory supplied cable.
1.1)
(Factory supplied cable)
1.2)
(Factory supplied cable)
2 Follow the same procedure as for the electrical heater wire
but connecting the extension cable to the wire-to-wire con-
nector in the Electrical Box 1 back side as shown in the figure.
Wire-to-wire LCD
connector (CN28)
46
(Extension cable)
(Extension cable)
29
28
(Extension cable)
(Extension cable)
Rear E-BOX 1
PMML0291A rev.2 - 09/2014

7.5.13 Levelling procedure


Indoor unit
Follow the same procedure explained in
alone (Without tank)
on the
and operation manual.

Domestic hot water tank
If it is necessary, adjust the height of the mounting foot as follows:
N O T E
All the procedure must be done before filling the water tank.
Adjust only the necessary mounting foot of the DHW tank with
the foot locknuts and when the tank is in the final position
(moving the DHWT after levelling can make it uneven again).
Start with all four feet screwed in as far as possible (factory
supplied position).
Use two or more people for levelling procedure.
Follow the process:
1 Loosen the locknut of the mounting feet which needs to be
extended (using a wrench).
2 Turn the mounting foot to extend the height (use the hexagon
or slot designed for this purpose in the shaft end).
3 When the mounting foot is in his end position, lock the locknut.
It may be necessary holding the foot to keep it from turning
while tightening the locknut. Use for this purpose the hexagon
or slot in the shaft end.
If it is needed to proceed with the levelling procedure with a sec-
ond foot (process 1 to 3), never work over one foot at same time.
When finish, all 4 locknut must be tightened firmly.
Hexagon and slot
for help in the
foot adjustment
process
Threaded shaft
Washer
Weld nut
Locknut
Foot
7 mm
Adjust the
foot's height
as needed
(2 options)
10 mm
Extend
Take in
Installation of indoor unit
YUTAKI S80 indoor unit Installation
Loosen locknut
17 mm
Lock the foot
Hold the foot
turning the
shaft to keep
locknut
it from turning
(2 options)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dhws195s-2.0h1eDhws260s-2.0h1e

Table of Contents