Sensor Setup

NOTE: Analog 1 is the designated control input for transducers. In Auto Mode, this input can be monitored
and used to control the run state and speed of the pump. Refer to
tion.
1.
From the Home screen, select the Settings icon.
2. Press the Sensors icon on the Settings screen.
3. Select an analog input to assign a sensor to it.
4. Select the appropriate description from the drop-down menu.
Options include Level, Discharge Pressure, Suction Pressure, and Flow.
NOTE: Flow can only be selected for Analog sensors 2, 3, and 4 for monitoring purposes only.
5. Set the Range Min by pressing the input box and entering the associated sensor value.
NOTE: Analog 1 can only accept sensors with a minimum value of 0.
6. Set the Range Max by pressing the input box and entering the associated sensor value.
7.
Select the appropriate units from the drop-down menu.
8. Press the button in the right-hand corner to view the M12 CONNECTOR
PIONOUT ANALOG INPUTS diagram.