Final Check - LG HA063M E1 Installation Manual

Backup heater
Table of Contents

Advertisement

3Way Valve (For Backup Heater Bypass)
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the unit.
Step 2. Find terminal block and connect wire as below. (in the unit)
18
19
20
L1
L2
N
2WAY VALVE
(A)
(NO)
(NC)
(N)
3WAY VALVE
(1) : Flow A means 'water flow from the unit to Buffer tank.' (Cooling)
(2) : Flow B means 'water flow from the unit to Backup Heater.' (Heating)

Final check

• Flow direction
- Water should not flow into Heater loop (B) in cooling mode.
- To verify the flow direction, check temperature at the water inlet of the under floor loop.
- If correctly wired, this temperatures should not be approached to 6°C in cooling mode.
• Noise or water pipe vibration while 3way valve operation.
- Due to surging effect or cavitation effect, noise or water pipe vibration can be occurred while
3way valve is operating.
- In that case, check followings :
Is water circuit (both under floor water loop and sanitary water tank loop) fully charged? If not,
additional water charging is required.
Fast valve operation yields noise and vibration. Appropriated valve operating time is 60~90
seconds.
WARNING
!
• When type of 2way valve is NO type, 3way valve should
select Flow A (bypass) when electric power is supplied to
wire (NO) and wire (N).
• When type of 2way valve is NC type, 3way valve should
select Flow A (bypass) when electric power is supplied to
wire (NC) and wire (N).
CAUTION
!
• 3way valve should be connected together with 2way valve in
terminal block.
• Keep the distance between 3way valve and Backup Heater
more than 0.5m.
• To prevent reverse flow, It is important to use one way
valve(check valve) to Backup Heater water outlet.