440 Fieldbus control through the embedded fieldbus interface (EFB)
Parameter
58.16
Communication
loss time
58.17
Transmit delay
58.25
Control profile
58.26
EFB ref1 type
58.27
EFB ref2 type
58.28
EFB act1 type
58.29
EFB act2 type
58.31
EFB act1
transparent
58.32
source
EFB act2
transparent
source
58.33
Addressing
mode
58.34
Word order
58.101
Data I/O 1
...
...
58.114
Data I/O 14
Setting for
fieldbus control
3.0 s (default)
0 ms (default)
ABB Drives
[0]
(default)
Speed or
frequency
(default
for 58.26) [0],
Transparent,
General,
Torque
[3] (default for
58.27),
Speed
[4],
Frequency
[5]
Speed or
frequency
(default
for 58.28) [0],
Transparent
(default for 58.29)
[1],
General
[2],
Torque [3],Speed
[4],
Frequency
[5]
Other
Mode 0
(default)
[0]
LO-HI
(default) [1]
For example, the
default settings
(I/Os 1...6 contain
the control word,
the status word,
two references and
two actual values)
RO/DIO control
word
[31],
AO1
data storage
[32],
AO2 data storage
[33],
Feedback
data storage
[40],
Setpoint data
storage
[41]
Function/Information
Defines the timeout limit for the
communication monitoring.
Defines a response delay for the drive.
Selects the control profile used by the drive.
See section
Basics of the embedded fieldbus
interface
(page 443).
Defines the types of fieldbus references 1 and
2. The scaling for each reference type is
defined by parameters 46.01...46.03. With
the
Speed or frequency
selected automatically according to the
currently active drive control mode.
Defines the types of actual values 1 and 2.
The scaling for each actual value type is
defined by parameters 46.01...46.03. With
the
Speed or frequency
selected automatically according to the
currently active drive control mode.
Defines the source of actual values 1 and 2
when the
58.26 EFB ref1 type (58.27 EFB
ref2
type) is set to Transparent.
Defines the mapping between parameters
and holding registers in the 400001...465536
(100...65535) Modbus register range.
Defines the order of the data words in the
Modbus message frame.
Defines the address of the drive parameter
which the Modbus master accesses when it
reads from or writes to the register address
corresponding to Modbus In/Out parameters.
Select the parameters that you want to read
or write through the Modbus I/O words.
These settings write the incoming data into
storage parameters
10.99 RO/DIO control
word,
13.91 AO1 data
data
storage,
40.91 Feedback data storage
40.92 Setpoint data
storage.
setting, the type is
setting, the type is
storage,
13.92 AO2
or