To unmount indoor unit
Press the 2
marks on the lower part of the indoor unit
and unlatch the tabs. Then lift the indoor unit and
unmount. (Fig. 42)
3-10. Drain Hose
a) The drain hose should be slanted downward to the
outdoors. (Fig. 43)
b) Never form a trap in the course of the hose.
c)
If the drain hose will run in the room, insulate the
hose with insulation* so that chilled condensation
will not damage furniture or floors. (Fig. 44)
* Foamed polyethylene or its equivalent is recom-
mended.
WARNING
Risk of Electric Shock
1:23 PM
Page 15
Do not supply power to the
unit or operate it until all
tubing and wiring to the out-
side unit are completed.
Indoor
unit
Insulation material
(Locally purchased)
must be used.
15
Push
Fig. 42
Slant
Drain
hose
Fig. 43
Condensation
Fig. 44