Enable Forcing Using Testmode Function Block; How To Change Binary Input/Output Signals Using Forcing; Forcing By Using Lhmi - Hitachi Relion REB670 Commissioning Manual

Table of Contents

Advertisement

1MRK 505 372-UEN Rev. K
IEC15000029 V1 EN-US
2.
Exit back to the root menu.
3.
Select Yes in the save dialogue box.
Once the IED is in test mode the yellow Start LED starts to blink.
9.8.2.2

Enable forcing using TESTMODE function block

Use the TESTMODE function block, appropriately configured in PCM600/ACT.
It may be convenient to control the input on mentioned component from, for example, an LHMI
function key or similar during commissioning to quickly and easily enter IED test mode.
9.8.3

How to change binary input/output signals using forcing

Once the IED is in IED test mode, the LHMI/PCM600 menus can be used to control input/output
signals freely.
9.8.3.1

Forcing by using LHMI

Editing a signal value directly
Edit the input/output value directly to select the desired logical level, by doing following:
1.
2.
Busbar protection REB670
Commissioning manual
Select the value line of the desired signal, see figure 10.
Press the Enter key to edit the value.
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 9
Testing IED operation
GUID-DD17B7D6-516F-4561-9D30-906B968EAFE0 v2
GUID-7DF9FAF1-68B1-49AF-9DE4-2A8D6F6FAEFE v2
GUID-D885671F-79E5-4B75-8777-B59E44F6FCFC v1
GUID-E0C115BE-3AD1-48C7-BA2D-29857CD3D3ED v1