Section 5
Mounting
5.3.4.2

Mounting procedure for side-by-side rack mounting

3
4
IEC04000456 V4 EN-US
Figure 7:
PosNo
1
2, 3
4
5
5.3.4.3

IED mounted with a RHGS6 case

A 1/2 x 19" or 3/4 x 19" size IED can be mounted with a RHGS case (6 or 12 depending on IED size).
The RHGS case can be used for mounting a test switch of type RTXP 24. It also has enough space for a
terminal base of RX 2 type for mounting of, for example, a DC-switch or two auxiliary relays.
26
1
2
Side-by-side rack mounting details.
The required torque for the screws is 3.5 Nm.
Description
Mounting plate
Screw
Mounting angle
Washer
© 2017 - 2023 Hitachi Energy. All rights reserved
3
Quantity
2
16
2
16
1MRK514026-UUS Rev. P
M11955-2 v4
Type
-
M4x6
-
M4x6
M11953-3 v4
670 series
Installation manual